7. Enter the sensors actual value (in this case depth) in the “
Actual value
” field.
8. Click on the “
Accept
” button to calculate the new slope and offset parameter values for the associated
channel. Clicking on the “
Cancel
” button terminates the procedure without altering the parameter
values.
For a short video of the procedure click "
Play
"-
MACE XCi User Manual - 215 -