Installing a MACE Doppler ultrasonic insertion sensor
WARNING: DO NOT cut the sensor cable. Re-termination of the sensor is highly
specialised and MUST be carried out at a MACE technical facility.
WARNING: Don’t mount the sensor at the top of the pipe as air pockets could give
unreliable readings. Don’t mount the sensor at the bottom of the pipe as silt build-up
can cover the sensor. Only mount the sensor between 2 and 5 o’clock as shown
below. MACE recommends mounting the sensor facing upstream wherever possible.
1. Using a 2” coring bit (hole saw) appropriate for the pipe material (eg. in a concrete pipe MACE
recommends the use of a diamond tipped bit), carefully core the pipe so that a clean cut is obtained.
NOTE: The hole should ALWAYS be only just bigger than the sensor head.
2. Measure and record the pipe wall thickness.
3. Attach a male 2” BSP or NPT nipple to the pipe
DIRECTLY CENTRED OVER THE HOLE
in a
manner suitable for the pipe material. This fitting must:
• Be at right angles to the flow
• Provide for a clean join inside the pipe (no burring etc)
• Be watertight
MACE XCi User Manual - 33 -
Summary of Contents for HVFlo XCi
Page 1: ......
Page 10: ...MACE XCi User Manual 10...
Page 18: ...MACE XCi User Manual 18...
Page 21: ...MACE XCi User Manual 21...
Page 50: ...MACE XCi User Manual 50...
Page 98: ...MACE XCi User Manual 98...
Page 173: ...MACE XCi User Manual 173...
Page 178: ...MACE XCi User Manual 178...
Page 211: ...For a short video of the procedure click Play MACE XCi User Manual 211...
Page 238: ...3 Unscrew the locking ring using the tool and remove completely MACE XCi User Manual 238...
Page 239: ...4 Remove the damaged ceramic depth sensor MACE XCi User Manual 239...
Page 250: ...MACE XCi User Manual 250...