Controls
Operation & Maintenance Manual 29
The MODBUS address map of registers is shown in the below table.
MODBUS Address
Meaning
Indicating Unit
NO
Write
1
46101
Chilled Water Out Temp
Chilled Water In Temp
Ref Cond Out Temp
Ambient Temp
Comp Exhaust Temp
Comp Capacity Rate
Running Hours
Running Status
Control Status
2
46102
3
46103
4
46104
5
46105
6
46106
7
46108
8
46109
9
46110
10
46115
11
06111
Actual Value x 10 [
°
C]
Actual Value x 10 [
°
C]
Actual Value x 10 [
°
C]
Actual Value x 10 [
°
C]
Actual Value x 10 [
°
C]
%
Hour
65: Starting, 66: Delaying, 67: Running
68: Shut -downing, 69: Stop
BIT0: Fault, BIT1: Comp Main MC
BIT2: Comp
MC, BIT3: Comp Y MC
Actual Value(5
°
C ~ 12
°
C) x 10 [
°
C]
0: Stop, 1: Start
YES
YES
-
-
-
-
-
-
-
-
-
-
-
Table 8