Service
Operation & Maintenance Manual
59
n
Compressor OCR (Over Current Relay)
The compressor OCR is thermal type and used to protect the compressor from overload condition. The OCR contact
used for the control system is normally closed and the OCR contact switch is to be opened if it detects excessive cur-
rent.
The OCR needs manual reset by switch on the OCR to be recovered to normal after tripping. The tripping point ranges
and factory settings are shown in the below table
n
Condenser Fan OCR
The condenser fan OCR is also thermal type and used to protect the condenser fan from overload condition. The OCR
contact used for the control system is normally closed, and the OCR contact switch is to be opened if it detects exces-
sive current.
The OCR needs manual reset by switch on the OCR to be recovered to normal after tripping. The tripping point ranges
and factory settings are shown in the below table.
Model
Range[A]
Trip[A]
RCAW090PBAA
165~235
177
RCAW1008BAA
165~235
173
Model
Range[A]
Trip[A]
RCAW090PBAA
6.5~8.5
8
RCAW1008BAA
4.5~6.5
6.2
Table 20
Table 21