General
Operation & Maintenance Manual 19
Parameter Setting
Fig. 7
Par. Setting
System Setting
Delay Setting
Content
Fan Start Temp3
Fan Start Temp2
Fan Start Temp1
Load Interval
Limit Temp
Low Temp
Outage DT
Restart DT
H Exhaust Temp
90.0
°
C
SET
SET
10.0~20.0
1.0~5.0
1.0~3.0
SET
1.0~3.0
34.0~37.9
29.0~33.9
25.0~28.9
29.0~200.0
35.0
°
C
30.0
°
C
26.0
°
C
60S
15.0
°
C
2.0
°
C
2.0
°
C
2.0
°
C
80.0~150.0
The system setting is composed of 3 screen cuts. Through the parameter setting, the control parameters of control oper-
ations can be identified and changed. To initiate the change, press the SET key. With confirming highlighted item after
pressing the SET key, the operator can change the value of a digit of the selected item by the arrow keys
or can
change the selected digit by the arrow keys
. After changing the value of all digits of the selected item, pressing
ENT makes the highlighted item to be changed to the next one. Pressing ESC during changing makes the changed to
be canceled.
Firstly, Fan control transition points (fan full opening, fan off1, and Fan off2) can be configured. From the transition
points, fan full opening means the condenser refrigerant leaving temperature setpoint for running all condenser fans.
When actual temperature is over the setpoint, all condenser fans must run. Similarly, the fan off1 means the condenser
refrigerant leaving temperature setpoint for running 8 condenser fans. And the fan off2 means the condenser refrigerant
leaving temperature setpoint for running 6 condenser fans. Consequently, minimum 6 condenser fans run when the
chiller operates, and the number of condenser fans is proportional to the condenser refrigerant leaving temperature. The
configurable range is shown in the below picture.
Secondly, system clock can be also changed here.
The compressor discharge alarm point temperature cannot be changed only, only informative to operator.
The load limit temp is the temperature setpoint where the capacity override is activated. When the chilled water leaving
temperature is over the value, the compressor is prevented from running with 100% capacity and the capacity of the
compressor is limited to 75%.
The anti-freezing temp is another method to protect the chiller from too low chilled water temperature additional to anti-
freezing switch shown in I/O display.