Operation
38 Chiller Air-cooled Screw
Condenser
Fan=ON
Water Pump
= ON
Alarm
Y Start
: M4
: M1=ON & M3=ON
: Oil Heater=OFF
: Oil Solenoid Valve(SV1)=ON
: Temp Leaving > Setpoint ?
MV1=
ON
: 25%
Alarm
M3 = OFF
DELTA Start
Stop
logic
No
No
Yes
Yes
0.5 Sec
4 Sec
9 Sec
Yes
3 Sec
Yes
No
No
: Flow S/W
: 30 - 60 sec
No
Yes
Yes
: M1=ON & M2=ON
Capacity
Control
Mid-pressure
Refrigerant
Valve Control
Alarm
Control
Condenser
Fan Control
: SV2
Y-DELTA START
STOP
Start
Contactor
Check
Flow
Check
Water
Temp.
Check
Comp.
Contactor
Check
Stop?
Fig. 16