Displayed Alarm
Message
Recognition
Possible Cause
Possible Remedy
Trouble Shooting
74 Chiller Air-cooled Screw
• Charge additional refrigerant or
review valve condition
• Repair comp
• Check ambient temperature
• Compressor discharge
temperature is over
≤
194°F(90°C) after the
compressor run
• Refrigerant flow rate insufficient
• Comp error
• Too high ambient temperature
Exhaust Temp
Alarm
• Check connection between PLC
and HMI unit
• Communication failure
• Communication failure between
the PLC and the HMI unit
Contact fault
alarm
• Replace FAN1A1B motor, check
magnetic contactor or relay
• Check FAN1A1B lock
• FAN1A1B magnetic
contactor contact input
or overload relay con-
tact input (switch off)
after the compressor
run
• Malfunction of FAN1A1B
• Condenser FAN1A1B overload
FAN1A1B Alarm
• Replace FAN2A3A motor, check
magnetic contactor or relay
• Check FAN2A3A lock
• FAN2A3A magnetic
contactor contact input
or overload relay con-
tact input (switch off)
after the compressor
run
• Malfunction of FAN2A3A
• Condenser FAN2A3A overload
FAN2A3A Alarm
• Replace FAN4A5A motor, check
magnetic contactor or relay
• Check FAN4A5A lock
• FAN4A5A magnetic
contactor contact input
or overload relay con-
tact input (switch off)
after the compressor
run
• Malfunction of FAN4A5A
• Condenser FAN4A5A overload
FAN4A5A Alarm