Service
52 Chiller Air-cooled Screw
■
Anti-freezing Switch
The anti-freezing switch is used to detect too low water temperature. The switch is normally closed and tripped when
the chilled water leaving temperature is under 35.6°F(2°C). The switch returns to the normal status when the tempera-
ture increases over 41°F(5°C). The Anti-freezing switch is installed on the evaporator.
Fig. 29