Oil Heater
■
Solenoid Valve
One of the Solenoid Valve is installed between the Flash Gas Tank where the oil separator is installed and the
other is installed between the oil filter and Flash Gas Tank. Valve on the compressor side is turned on during Full
Load operation, and off during other operations. Valve on the oil filter side is turned on when the unit is operating
to pass the oil to the compressor, and off when the operation stops to prevent the oil from back flowing.
The oil heater prevents poor lubrication due to too low viscosity. The oil heater is also installed on the oil sepa-
rator. The 150W oil heater has 220VAC power input.