Start-up
Operation & Maintenance Manual
35
Flow Rate
The basic flow rate of the chiller must follow the values of the table showing the maximum, minimum and
designed flow rate.
Higher or lower flow rates are permitted to make the lower or higher temperature rise.
In order to assure appropriate heat exchange and turbulent flow inside the evaporator, the flow rate must
exceed the Minimum flow rate.
gpm
l
/s
gpm
l
/s
gpm
l
/s
RCAW100*BAA
RCAW090*BAA
116.9
7.4
234
14.7
467.6
29.5
107.7
6.8
215
13.6
430.8
27.2
Maximum
Model
Minimum
Norminal
Table 10
Compact