Troubleshooting Guide
170
Outdoor Unit
Communication
error (Inverter
PCB ’ Main PCB )
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
52
The inverter PCB cannot
receive the signal from the
Main PCB
Concerned
Remote
Controller
Outdoor unit
1. Power line or the communication
line is not connected
2. Communication cable is
Open/Short
3. Outdoor main fuse is damaged
4. Defective outdoor Main/inverter
PCB.
■
Defect inspection method
1) Check whether the communication cable connection is normal.
Otherwise, check the communication cable and replace if required.
2) Check whether the Outdoor Main /inverter PCB is working on power input
Check whether the PCB orange color LED is blinking.
(if the power input and the communication is normal then the LED is blinking)
3) Check the outdoor Main / inverter PCB and replace the PCB if required .
Communication connector &
LED in the main PCB
Communication connector &
LED in the inverter PCB
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...