Troubleshooting Guide
154
Outdoor Unit
Excessive rise of
the inverter
comp.(A)
discharge temp .
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
32
Inverter comp. Off due to
the excessive rise in dis-
charge temp
Concerned
Remote con-
troller
Panel Display
Outdoor unit
1. Inverter comp. discharge temp.
sensor defect
2. Refrigerant shortage / leakage
3. Defective LEV
4. Defective Liquid Injection Valve
5. Defective Hot Gas Bypass Valve
■
Defect inspection method :
1) In case there is no actual rise of the discharge temp of the inverter comp.(A) but the sensor shows abnormal
rise of the temp, then please replace the discharge pipe sensor
- Discharge temp sensor 10°C = 362k
Ω
, 25°C = 200k
Ω
,
50°C = 82k
Ω
, 100°C = 18.5k
Ω
In case there is no actual rise of the discharge temp of the inverter comp.(A),
then please replace the outdoor MAIN PCB.
2) Check the indoor / outdoor LEV / Hot gas / Liquid Injection valve connector connecting condition.
Excessive rise of
the inverter
comp.(B)
discharge temp .
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
33
Inverter comp. Off due to
the excessive rise in dis-
charge temp
Concerned
Remote con-
troller
Panel Display
Outdoor unit
1. Inverter comp. discharge temp.
sensor defect
2. Refrigerant shortage / leakage
3. Defective LEV
4. Defective Liquid Injection Valve
5. Defective Hot Gas Bypass Valve
■
Defect inspection method :
1) In case there is no actual rise of the discharge temp of the inverter comp.(B) but the sensor shows abnormal
rise of the temp, then please replace the discharge pipe sensor
- Discharge temp sensor 10°C = 362k
Ω
, 25°C = 200k
Ω
,
50°C = 82k
Ω
, 100°C = 18.5k
Ω
In case there is no actual rise of the discharge temp of the inverter comp.(B),
then please replace the outdoor MAIN PCB.
2) Check the indoor / outdoor LEV / Hot gas / Liquid Injection valve connector connecting condition.
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...