Service Manual
169
Troubleshooting Guide
Excessive capaci-
ty
(Indoor capacity
is in excess )
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
51
The combined spec of the
indoor units excess the
capacity of the outdoor unit
Concerned
Remote
Controller
Outdoor unit
1. Excess of indoor capacities more
than 130% of the outdoor unit
2. Auto-Addressing is not in operation
.
3. The communication cable connec-
tion error ie the indoor unit connect-
ed to some other outdoor unit has
the communication cable mixed up
or confused
■
Defect inspection method
1) Check the total capacity of the all indoor units and compare it with the 130% of the capacity of the outdoor unit .
2) Check whether the communication cable of some of the indoor unit is connected to some other outdoor unit
(Refer to CH05)
3) Please operate the Auto-Addressing.
4) In case the error code is still in display even when the above given contents are normal then please replace the
PCB .
5) In case the error code exists even after the outdoor PCB is replaced then please check the indoor PCBs one
by one
To carry out Auto-Addressing
function, press red button until
you see '88 'displayed on 88
segment as shown in left
side picture.
7
segment
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...