Service Manual
93
2.1 Oil return control
2.1.1 Oil return control on cooling mode
■
High pressure limit
■
Low pressure limit
■
Oil return operation time : 4 min for running step
■
Starting condition:every 6 hours operate
Inv
Compressor
Normal
Pressure
limit
Fan
Main LEV
4 way valve
Subcooling LEV
37Hz + 37Hz
90Hz + 90Hz
20Hz + 20Hz
30Hz + 30Hz
50Hz + 50Hz
20Hz + 20Hz
0 Hz
Full open
Off
min.
Starting
Component
Pressure range
Low pressure
≤
229 kpa
Low pressure
≥
242 kpa
Compressor combination
Refer to combination table
Normal
Sub unit
compressor
All off
Hot gas bypass
valve
Off
High pressure
control
Full open
Off
min.
Running
On
Suction pipe temp.
control
High pressure
control
Full open
Off
min.
Ending
Off
Off
Fan
Keep state
Starting
Indoor unit
Thermo on unit
LEV
Oil return
pulse
Keep state
Running
Oil return operation
pulse
Keep state
Ending
Return to
base pulse
Thermo off unit
LEV
Close pulse
Oil return operation
pulse
Close pulse
Pressure range
Low pressure
≤
3189 kpa
Low pressure
≥
3189 kpa
Compressor combination
Refer to combination table
Normal
2. Special control
Function
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...