Service Manual
171
Troubleshooting Guide
Communication
error (indoor ›
Main PCB )
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
53
The indoor cannot receive
signal from the Main PCB
Concerned
Remote
Controller
Outdoor unit
1. The communication cable is not
connected
2. Communication cable is cut or short
3. Defective outdoor Main / indoor
PCB
■
Defect inspection method
1) Check the indoor unit's control box's power supply and communication connecting condition (terminal block )
2) Check if the communication cable is short or open and remove the cause if any
(Open confirmation :
After the power OFF short the two cables with each other and measure the resistance with a tester ’ If above 5
Ω
then it is Open)
(Short confirmation :After power OFF separate the cables and measure the resistance with a tester › If below
5
Ω
then it is short )
3) In case there is no error in above given cases 1~2 the separate all the communication cables and recheck after
connecting the indoor units individually
(The error code is displayed when the defective PCB is connected to the indoor unit) › Replace the concerned
indoor unit's PCB .
4) In case one indoor or a few indoor has 'CH53' error display :
Re operate the Auto-Addressing and check whether the all indoor units have Auto-Addressing setting .
(After the power ON, make sure to operate the Auto-Addressing after one minute )
› In case the any PCB has not got the Auto-Addressing then recheck the communication cable and replace the
indoor PCB if required .
5) Make sure to separate the power line (AC220/380V) and the communication line by at least 30 cm
CAUTION
• In case you replace the communication cable with the power cable by mistake then al indoor units PCB can be
damaged
Outdoor 3 phase
power supply
wrong wiring
(Phase omission )
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
54
Wrong wiring at the out-
door 3 phase
(Phase omission )
Concerned
Remote
Controller
Outdoor unit
1. Defective inverter PCB
2. R, S, T power not connected
3. Main Fuse damaged
■
Defect inspection method
1) Check the outdoor Main fuse .
2) If the error code exists even after replacing the outdoor PCB then request the building's electric in charge to
recheck the power supplied.
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...