Service Manual
117
2.2 Fan Motor
(1) The fan motor does not
operate.
Does failure appears
again when starting
operation?
(2) Vibration of the fan
motor is large.
1) When power supply is
abnormal
2) For wrong wiring
3) For failure of motor
4) For defective fuse
5) For failure of circuit board
* Modify connection status in front of or at the rear of
the breaker, or if the power terminal console is at
frosting condition.
* Modify the power supply voltage is beyond speci-
fied scope.
* For following wiring.
1. Check connection status.
2. Check contact of the connector.
3. Check that parts are firmly secured by tightening
screws.
4. Check connection of polarity.
5. Check short circuit and grounding.
* Measure winding resistance of the motor coils.
8.9
Ω
±5%(75°C)
* Replace the fuse if there is defect (Fuse 800V
30A).
Replace the circuit board in following procedures if
problems occur again when powering on and if
there are no matters equivalent to items as speci-
fied in above 1) through 4).
(Carefully check both connector and grounding
wires when replacing the circuit board.)
1. Replace only fan control boards.
If starting is done, it means that the fan control
board has defect.
2. Replace both fan control board and the main
board.
If starting is done, it means that the main board
has defect.
3. If problems continue to occur even after counter-
measure of No.1 and No.2, it means that both
boards has defect.
Checking Item
Symptom
Countermeasure
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...