Troubleshooting Guide
130
Indoor Unit
[In case only one Indoor Unit or only few Indoor Units display 'ch05' error ]
1) Re-operate the Auto-Addressing function and then confirm the Auto-Addressing in all Indoor Units.
Auto-Addressing can be confirmed at the Wired Remote Controller.
In case of the Indoor Units not having the Wired Remote Controller, check the blinking counts of the Indoor
Unit panel (Auto-Addressing must be operated after minimum 1 minute of power On ) › Check the Indoor Unit
not having Auto-Addressing and replace the concerned unit PCB if required.
2) Make sure to separate the communication wire and the power line (AC220/380V ) by a distance of minimum
30 cm.
CAUTION
• In case you replace the communication wire by power 220V line, then the connected PCB gets damaged
or burnt.
To carry out Auto-Addressing
function, press red button until
you see '88 'displayed on 88
segment as shown in left
side picture.
7
segment
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...