Service Manual
165
Troubleshooting Guide
Outdoor Unit air
temperature sen-
sor error
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
44
Sensor measured value is
not normal
(Open/Short)
Concerned
Remote con-
troller
Panel Display
Outdoor unit
1. Defective connection of the temp.
sensor
2. Defective temp. sensor (Open /
Short)
3. Defective Outdoor Unit PCB
The pipe sensor
error of the
Outdoor Unit’s heat
exchanger
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
45(Heat
exchanger
Upper parts)
48 (Heat
exchanger
Lower parts)
Sensor measured value is
not normal
(Open / Short)
Concerned
Remote con-
troller
Panel Display
Outdoor unit
1. Defective connection of the temp.
sensor
2. Defective temp. sensor (Open /
Short)
3. Defective Outdoor Unit PCB
Comp. suction
temp. sensor error
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
46
Sensor measured value is
not normal
(Open/Short)
Concerned
Remote con-
troller
Panel Display
Outdoor unit
1. Defective connection of the temp.
sensor
2. Defective temp. sensor (Open /
Short)
3. Defective Outdoor Unit PCB
■
Defect inspection method s
1) Check the temp. sensor connecting condition and also the lead wire connecting condition.
2) Check whether the temp. sensor resistance value is normal ? Otherwise, replace the sensor.
- Air temp. sensor : 10°C = 20.7k
Ω
, 25°C = 10k
Ω
, 50°C = 3.4k
Ω
- Pipe temp. sensor : 10°C = 10k
Ω
, 25°C = 5k
Ω
, 50°C = 1.8k
Ω
3) In case the sensor connection and the resistance value is normal, then please replace the outdoor PCB .
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...