Trouble Shooting Guide
2. Checking Method for Key Component
2.1 Compressor
Check and ensure in following order when error related with the compressor or error related with power occurs
during operation:
[Cautions when measuring voltage and current of inverter power circuit]
Measuring values may differ depending on measuring tools and measuring circuits since voltage, current in the
power supply or output side of the inverter has no since waveform.
Especially, output voltage changes when output voltage of the inverter has a pattern of pulse wave.
In addition, measuring values appear largely differently depending on measuring tools.
1) If using a movable tester when checking that output voltage of the inverter is constant (when comparing rela-
tive voltage between lines), always use an analog tester. Especially exercise particular caution if the output
frequency of the inverter is low, when using a movable tester, where change of measured voltage values is
large between other lines, when virtually same values appear actually or where there is danger to determine
that failure of the inverter occurred.
2) You can use rectification voltmeter (
) if using commercial frequency tester when measuring output values
of the inverter (when measuring absolute values). Accurate measuring values cannot be obtained with a gen-
eral movable tester (For analog and digital mode).
1
2
Is how long power on during
operation?
Does failure appears again
when starting operation?
Method to measure insulation
resistance
Method to measure coil
resistance
1) Power on for 12 hours or more
2) Power on for 12 hours or less
1) The compressor stops and same
error appears again.
2) If output voltage of the inverter is
stable *1
3) If output voltage of the inverter is
unstable or it is 0V.
(When incapable of using a digi-
tal tester)
* Go to No.2.
* Go to No.2 after applying
power for designated time (12
hours).
* Check IMP may fail.
* Check coil resistor and insula-
tion resistor. If normal, restart
the unit. If same symptom
occurs, replace the compres-
sor.
* Insulation resistor: 2MW or
more
Coil resistor: U-V: 1.083
Ω
V-W: 1.123
Ω
W-U: 1.096
Ω
* Check the IPM.
If the IPM is normal, replace
the inverter board.
* Check coil resistor and insula-
tion resistor.
No.
Checking Item
Symptom
Countermeasure
Comp.
Tester
V
U
W
Ω
Figure 2.
Comp.
pipe
Figure 1.
Ω
Tester
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...