Service Manual
127
Troubleshooting Guide
Indoor Unit room temp.sensor error
Unit inlet pipe temp.sensor error
(Indoor Unit)
Outlet pipe temp. sensor error
(Indoor Unit)
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
01
02
06
Indoor Unit
sensor open
or short
Concerned
Remote con-
troller
Panel Display
1. Sensor wrong connection
2. Sensor open/Short
3. Defective Indoor Unit PCB
4. Defective Sensor
■
Defect inspection method :
1) Check the connecting point of the sensor with the PCB (Sensor's Connector).
Is the sensor connecting condition correct ? Otherwise, reconnect the sensor at the correct position.
2) Remove the sensor and measure its resistance with a tester.
Room temp sensor : 10°C = 20.7k
Ω
: 25°C = 10k
Ω
: 50°C = 3.4k
Ω
Pipe temp sensor : 10°C = 10k
Ω
: 25°C= 5k
Ω
: 50°C = 1.8k
Ω
3) Replace the sensor if it is not having a correct resistance value.
4) If there is no problem with the sensor and the sensor connection then replace the Indoor Unit PCB.
• Panel Display indication method : Error code and the LED blinking counts are indication.
Communication error
between Indoor Unit and
the Wired Remote
Controller
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
03
In case the wired
Remote Controller
cant receive the
the signal from the
Indoor Unit
Concerned
Remote
Controller
Panel Display
1. Defective wired Remote controller.
2. Defective Indoor Unit PCB .
3. Defective Connector connection
4. Defective wire of the Wired Remote
Controller
■
Defect inspection method :
1) Check the connection point of the Wired Remote Controller (Connecting Connector).
2) In case the Wired Remote Controller's cable is installed near the AC power line, then they must be separated by
distance of at least 30cm.
3) In case the replaced Remote Controller has no defect, then the originally installed Remote Controller is defec-
tive.
4) In case the error code exists even after the replacement of the Remote Controller, then the Remote Controller is
not defective and hence only Indoor Unit PCB should be replaced.
5) In case error code exists even after the replacement of the Wired Remote Controller and the Indoor Unit PCB,
then replace the cable connecting the Wired Remote Controller and Indoor Unit.
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...