Function
4.2 Instant indoor unit checking mode
- Indoor units can be turned on/off by outdoor unit without central controller or central control address setting with
this function.
- All indoor units will be turned off and be wait for 3 min. at the beginning.
- All indoor units can be run on only one mode, cooling or heating by dip switch setting.
- In instant indoor unit checking mode, the indoor unit cannot be controlled by the wired remote controller and
there is no display in indoor unit's remote controller. If the indoor unit is turned on/off by the remote controller, it
has no effect on the unit.
Red button : push 3 times in 3 sec.
Instant indoor unit checking mode starts
Red button pushed : Next indoor unit
Black button pushed : On
→
Off, Off
→
On
(3 times)
Red button pushed : Next indoor unit
At last indoor unit,
Red button pushed : Return to 1
st
unit
Dip switch setting
1 on : cooling, 1,2 on : heating
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...