70
Indoor Unit
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
3
/min x 35.3
Notes:-
1. Capacities are based on the following conditions:
Cooling
• Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating
• Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. L.E.V.: Linear Expansion Valve
5. To be added for more available Models
Type
Model
Unit
W
Cooling Capacity
kcal/h
Btu/h
W
Heating Capacity
kcal/h
Btu/h
Casing
Dimensions (W*D*H) Body
mm
inch
Coil
Rows x Columns x FPI
Face Area
m
2
Type
Motor Output x Number
W
Running Current
A
Fan
Air Flow Rate(H/M/L)
cmm
cfm
External Static Pressure
Pa
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.)
mm
Net Weight
kg(lbs)
Noise Level(Sound Press, 1.5m, H/M/L)
dBA±3
Power Supply
Ø / V / Hz
Refrigerant Control
Power cable
mm
2
Transmission cable
mm
2
Ceiling Concealed Duct(High Static)(Preliminary)
ARNU36GBGA0
ARNU42GBGA0
ARNU48GBRA0
10,600
12,300
14,100
9,100
10,600
12,100
36,200
42,000
48,100
11,900
13,800
15,900
10,200
11,000
13,200
40,600
43,800
51,200
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
1182x450x298
1182x450x298
1230x590x380
46.5x17.7x10.2
46.5x17.7x10.2
48.4x23.2x15
3x12x21
3x12x21
3x13x19
0.26
0.26
0.38
Sirocco Fan
Sirocco Fan
Sirocco Fan
390
390
390
2.3
2.30
2.30
28.4/25.3/21.8
32.0/28.4/27.2
45/40/34
1003/893/770
1130/1003/960
1589/1413/1201
78.5
78.5
98.1
Direct
Direct
Direct
BLDC
BLDC
BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Foamed polystrene
Foamed polystrene
-
-
-
Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor
Ø9.52(3/8)
Ø9.52(3/8)
Ø9.52(3/8)
Ø15.88(5/8)
Ø15.88(5/8)
Ø15.88(5/8)
25
25.0
25.0
38(83.8)
38(83.8)
53(117)
44/42/40
46/44/42
48/46/44
1, 220 ~ 240, 50
1, 220 ~ 240, 50
1, 220 ~ 240, 50
1, 220, 60
1, 220, 60
1, 220, 60
LEV
LEV
LEV
CV2.0 X 3C
CV2.0 X 3C
CV2.0 X 3C
CVV-SB 1.25 X 2C
CVV-SB 1.25 X 2C
CVV-SB 1.25 X 2C
Specifications
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...