Troubleshooting Guide
146
Outdoor Unit
Inverter comp. dri-
ving voltage
charging defect
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
23
Problem in DC charging
voltage after operating
relay On
Concerned
Remote con-
troller
Panel Display
Outdoor unit
1. Looseness of DC link terminal .
2. Damage operating relay
3. Capacitor damage
4. Three phase current diode damage
5. Abnormal power voltage
6. IPM damage
7. Defective sensing circuit of the
invert PCB
■
Defect inspection method : Refer error code 21
1) Check whether the starting relay / magnetic contactor at the control box are normal ?
(After about 30 seconds of operation the voltage at the IPM P/N terminal should be above 450Vdc)
2) In case the voltage is below 450Vdc,
- Make sure that the outdoor main input voltage is (360Vac~410Vac),
- Make sure that the magnetic contactor coil resistance (400~700
Ω
) when the power is Off and also check the
connecting conditions,
- Check whether the comp capacitor connection and the outer shape is normal.
(In case of any abnormality there is a shape change or expansion of the capacitor outer body )
3) Compressor insulation and the coil resistance and 3 phase rectification diode should also be checked.
(Refer error code 21).
4) In case the error code is still displayed after solving the issue from clause 1)~3), then replace the inverter PCB.
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...