Service Manual
161
Troubleshooting Guide
Comp. discharge
pipe temp. sensor
error
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
41
Sensor measurement
value is abnormal (Open /
Short)
Concerned
Remote con-
troller
Panel Display
Outdoor unit
1. Defective connection of the comp.
discharge pipe temp. sensor
2. Defective discharge pipe temp.
sensor of the comp (Open/Short)
3. Defective outdoor PCB
■
Defect inspection method
1) Check the comp. discharge pipe temp. sensor and the lead wire connecting condition.
2) Check whether the sensor resistance value is normal ? Otherwise, replace the sensor.
- Comp. discharge pipe temp. sensor : 10°C = 362k
Ω
, 25°C = 200k
Ω
, 50°C = 82k
Ω
, 100°C = 18.5k
Ω
3) In case the sensor connecting condition and the resistance value are normal, then please replace the outdoor
PCB.
4) If "n1" is displayed at the 7 segment, check comp A
If "n2" is displayed at the 7 segment, check comp B
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...