Troubleshooting Guide
136
Outdoor Unit
Protection of
Inverter compres-
sor from over cur-
rent (Detection of
over 80A per
1.8ms IPM )
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
21
Defective inverter com-
pressor, Inverter element
(IPM) defect
Concerned
Remote controller
Panel Display
Outdoor unit
1. Over current detection at the invert-
er compressor (U,V,W)
2. IPM Overheating .
3. Insulation damage of the compres-
sor / motor damage
5. Low input voltage at the outdoor
6. Inverter compressor terminal dis-
connected or loose .
7. Inverter PCB/IPM PCB defect
■
Defect inspection method :
1) Check whether the insulation of the compressor, motor coil resistance is normal ? Otherwise, replace the com-
pressor .
- Motor Coil resistance normalcy : Resistance between each terminal of Inverter compressor =1.33
Ω
±7% ,
Resistance between the each terminal of the constant speed compressor =1.83
Ω
±7% (The 3 measured value
must be similar)
- Insulation normalcy : Resistance between the compressor terminal and the product body = Above 2M
Ω
(Measured within specified time after the compressor stop )
2) Check whether the IPM/3 phase rectification Diode is normal ? Otherwise, replace the IPM/ Diode .
- Tester : After setting the Diode mode , test with the tester probe in + ,- sequence.
- IPM:'U-P/V-P/W-P' measurement : 0.3~0.6 V, Reverse polarity measurement :Above 2.6 V
'N-U/N-V/N-W' measurement : 0.3~0.6 V, Reverse polarity measurement : Above 2.6 V
- 3 phase rectification diode : ~ & + / ~ & + / ~ & +' sequential measurement : 0.3~0.6 V,
Reverse polarity measurement : Above 2.6V
3) Check whether the input voltage is 360V~410V(AC).
4) Check the balance between each phase at the main breaker of the building (phase distribution ) (Below 5~10V).
5) Check whether the terminal connection is normal ?
(Comp connecting terminal, IPM connecting terminal, diode connecting terminal, capacitor connecting terminal)
6) Check whether the IPM Pin connecting to PCB soldering is normal ?
(Dismantle the PCB and check the soldering at the back side of the PCB .)
In case if any abnormality please replace the IPM PCB.
7) Check whether the Outdoor Unit fan is working ? In case of any abnormality please check the outdoor fan
(Refer to CH105~CH108)
8) Check whether the supplied power is normal or insufficient.
9) After the inspection, check whether the input power to the IPM during the trial run is 450V~560V(DC).
(Set the tester at the DC mode)
Check the IPM terminal connecting condition.
(Comp connecting terminal, IPM connecting terminal, diode connecting terminal, capacitor connecting terminal )
10) Measure the current at each phase (U,V,W) of the inverter compressor during the trial run after the completion
of the inspection.
In case the deviation between the current in each phase is above 1.5A then replace the PCB .
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...