Service Manual
179
Troubleshooting Guide
Sensor error at
the outdoor Liquid
Refrigerant pipe
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
113
Abnormal value of Sensor
measurement
(Open/Short)
Concerned
Remote
Controller
Outdoor unit
1. Defective temp sensor connector
connection
2. Defective temp sensor Open/Short)
3. Defective outdoor PCB
Sensor error at
the outdoor sub
cooling inlet or
outlet
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
114(Main
Sub cool
inlet)
115(Main
Sub cool
outlet)
Abnormal value of the sen-
sor measurement
(Open/Short)
Concerned
Remote
Controller
Outdoor unit
1. Defective temp sensor connector
connection
2. Defective temp sensor
(Open/Short)
3. Defective outdoor PCB
■
Defect inspection method
1) Check the temp sensor connector connecting condition and lead wire.
2) Is the temp sensor resistance value normal? Otherwise, replace the sensor
- Pipe temp sensor : 10°C = 10k
Ω
: 25°C = 5k
Ω
: 50°C = 1.8k
Ω
3) In case the sensor connection and the resistance value is correct then replace the outdoor PCB .
Communication
error between the
Main PCB and the
fan PCB
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
108
Communication error
between the Main PCB
and the fan PCB
(Fan › outdoor , outdoor ›
fan )
Refer to CH105
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...