Service Manual
145
Troubleshooting Guide
Maximum over
current
(MAX CT)
Error
Code
Error Contents
Meaning
Main Causes
Error display
position
22
The current flowing at the
CT sensing circuit should
be more than the maxi-
mum value of the current
tolerance for the product .
Concerned
Remote con-
troller
Panel Display
Outdoor unit
1. Comp. damage
2. Current sensing sensor damage
(CT)
3. Low input voltage
4. Comp. terminal is disconnected or
loose .
5. Abnormality at the Outdoor /Indoor
Unit fan
7. Cover or chocking (Outdoor Unit
covering during cooling mode /
Filter chocked at the Indoor during
heating mode )
6. Defective inverter PCB/IPM PCB .
■
Defect inspection method : Refer error code 21
1) Check whether the current measured at the R phase during operation is above 18~20A ?
In case the current measurement is normal (During compressor operation :3~16A), Replace the inverter PCB.
2) In case the current is above 18~20A, check the comp. insulation and the motor coil resistance
(Refer error code 21)
→
In case the resistance is abnormal, then replace the comp.
3) Check whether the Main input power is 360Vac~410Vac.
Check whether a deviation exists between the main power voltage of each phase (Below 5~10V)?
In case there is a deviation in the required power supply in each phase or the abnormality of the input voltage,
then please request the building electricity in charge to change the power supply accordingly.
4) Please remove any obstacle in path of the outdoor heat exchange and also clean the Indoor filter.
5) Check whether the IPM Pin connecting PCB soldering is normal ?
(Check the PCB soldering at the back side of PCB after dismantling the PCB)
In case of any abnormality, then please replace the IPM PCB .
6) Measure the current between each phase of the inverter comp (U,V,W) during the trial run after the inspection .
In case of current deviation between each phase is above 1.5A, then replace the inverter PCB.
Measure current of Phase 'R'
Summary of Contents for ARNU Series
Page 13: ...Service Manual 13 External Appearance 2 2 Outdoor Units ARUN1008F20 10HP ...
Page 16: ...16 ...
Page 17: ...Service Manual 17 Indoor Units ...
Page 18: ...18 Indoor Unit ...
Page 30: ...30 Indoor Unit ...
Page 44: ...44 Indoor Unit ...
Page 79: ...Service Manual 79 Outdoor unit ...
Page 88: ...88 Outdoor Unit 5 Wiring Diagrams Wiring Diagrams ...
Page 112: ...112 Outdoor Unit ...
Page 113: ...Service Manual 113 Trouble shooting guide ...
Page 137: ...Service Manual 137 Troubleshooting Guide Resistance measure between phases of compressor ...
Page 142: ...Troubleshooting Guide 142 Outdoor Unit Connector of reactor Connectors of 3phase diode ...
Page 143: ...Service Manual 143 Troubleshooting Guide Connectors of capacitor Check IPM PCB ...
Page 150: ...Troubleshooting Guide 150 Outdoor Unit Pressure switch CHECK VALVE ...
Page 152: ...Troubleshooting Guide 152 Outdoor Unit Measure power input of outdoor unit ...
Page 153: ...Service Manual 153 Troubleshooting Guide Measure power input of outdoor unit ...
Page 156: ...Troubleshooting Guide 156 Outdoor Unit Liquid injection by pass valve ...
Page 157: ...Service Manual 157 Troubleshooting Guide Measure resistance of LEV coil ...
Page 158: ...Troubleshooting Guide 158 Outdoor Unit Heater ...
Page 168: ...Troubleshooting Guide 168 Outdoor Unit Measure input power of outdoor unit ...
Page 172: ...Troubleshooting Guide 172 Outdoor Unit Check main fuse of out door unit ...
Page 176: ...Troubleshooting Guide 176 Outdoor Unit Fan IPM ...
Page 178: ...Troubleshooting Guide 178 Outdoor Unit Measure input power of fan main PCB ...
Page 183: ...Service Manual 183 Exploded View Replacement Parts List ...