Lift control interface
(M = 1)
Configuration example 1 :
8 floors building. Floors 4 to 8 are “PRIVATE” floors and each floor has 4 apartments. Floors 1 to 3 are “PUBLIC” floor and each floor has 1 entrance panel. The entrance panel adresses are
1 to 3 in correspondance with the 1 to 3 floor number. By setting delay time to 20 seconds (CF7 = 2), the interface configuration value and the correspondance between device OUTPUT
and Entrance panel/Internal unit floor will be as follows
(M = 1)
Configuration example 2 :
14 floors building. Floors 2 to 14 are “PRIVATE” floors and each floor has 4 apartments. The 1.st floor is the “PUBLIC” floor and has 1 entrance panel. N°2 lift control interface are requested
to manage this system. By setting delay time to 10 seconds (CF7 = 1), the configuration values of the two interfaces will be as follows :
Configuration
WARNINGS :
- OUTPUT 1 to 5 will manage the corresponding “PRIVATE” floors 4 to 8.
- OUTPUT 6 to 8 will manage the “PUBLIC” floors 1 to 3.
WARNING
- By this configuration method, DEVICE 1 (OUTPUT 8) will manage the 1.st floor (PUBLIC floor).
OUTPUT 1 to 7 will manage floors 2 to 8 (PRIVATE floors). DEVICE 2 (OUTPUT 1 to 6) will manage floors 9 to 14 (PRIVATE floors).
en
CONFIGURATION PLACE
CONFIGURATION VALUE
OUTPUT (N)
EP address/IU floor
CF1
0
OUTPUT1
IU floor 4
CF2
4
OUTPUT2
IU floor 5
CF3
0
OUTPUT3
IU floor 6
CF4
4
OUTPUT4
IU floor 7
CF5
5
OUTPUT5
IU floor 8
CF6
3
OUTPUT6
EP address 1
CF7
2
OUTPUT7
EP address 2
M
1
OUTPUT8
EP address 3
CONFIGURATION PLACE
CONFIGURATION VALUE
DEVICE 1
DEVICE 2
CF1
0
0
CF2
2
9
CF3
0
0
CF4
4
4
CF5
7
6
CF6
1
0
CF7
1
1
M
1
1
Summary of Contents for D45 SYSTEM
Page 2: ......
Page 4: ......
Page 8: ......
Page 9: ...GENERAL FEATURES...
Page 36: ......
Page 37: ...GENERAL RULES FOR INSTALLATION...
Page 82: ......
Page 83: ...WIRING DIAGRAMS...
Page 102: ......
Page 103: ...WIRING DIAGRAMS VARIANTS...
Page 116: ......
Page 117: ...CATALOGUE...
Page 122: ......
Page 123: ...TECHNICAL SHEETS...