User Manual Of EL7-EC** AC Servo
286
Error
code
Main Sub
Display: “
Er 813”
81
3
Error description: Protection request from boot state
Cause
Driver receives a transition request to boot state
The status of the
error can be detected
Initialize the conversion to a boot
The result status
initialization
Solution
Verify if driver software version supports this state transition
Error
code
Main Sub
Display: “
Er 814”
81
4
Error description: Invalid firmware
Cause
Firmware not matched with driver
The status of the
error can be detected
BOOT/INIT
The result status
Keeping in the detection status
Solution
Return driver to supplier to update firmware
Error
code
Main Sub
Display: “
Er 815”
81
5
Error description: Invalid mailbox configuration under boot state
Cause
Boot state action not supported under current configuration
The status of the
error can be detected
Initialize the conversion to a boot
The result status
Initialization
Solution
Verify if EL7EC software version supports action under this state.
Error
code
Main Sub
Display: “
Er 816”
81
6
Error description: Pre-Op status is invalid for the mailbox configuration
Cause
The synchronization manager configuration under Pre-Op is invalid
The status of the
error can be detected
pre-operation
The result status
initialization
Solution
1. Verify if XML file version is consistent with software version
2. EtherCAT slave controller error, please contact technical support