105
item Controller BL 1-04 /C
― Product manual
Group 72: PROFINET
72-0
PROFINET: initialisation
error
Replace the PROFINET module.
72-1
PROFINET: bus error
Communication is not possible, e.g. because the bus cable has been disconnec
-
ted. Check the wiring and restart the PROFINET communication.
72-2
PROFINET: range overflow
Mathematical error during the conversion of physical units.
Adapt the parameterisation.
72-3
PROFINET: invalid IP
configuration
Check whether the IP address, subnet mask and gateway address are valid or
permissible. Change the IP configuration.
72-4
PROFINET: invalid device
name
Use a valid PROFINET device name (Name of Station).
72-5
PROFINET: defective module Replace the PROFINET module.
72-6
PROFINET: invalid /unsup
-
ported indication
The PROFINET feature that has been used is not supported by the module.
Please contact the Technical Support team.
72-7
PROFINET: different module
configuration Master/Slave
Check whether the telegram lengths set in the PROFINET telegram editor match
the setting in the master.
72-8
PROFINET: failure in cyclic
data
Check wiring.
72-9
PROFINET: communication
error
Check the telegram configuration in the master.
Group 73: PROFINET
73-0
PROFIenergy: state not
possible
Request the PROFIenergy state again when the motor is stopped.
73-1
PROFINET: wrong firmware
found
Please contact the Technical Support team.
Group 78: NRT communication
78-0
NRT: frame send error
In general, no measure is required. It may be helpful to reduce the bus load, e.g.
by reducing the number of devices connected to a branch.
Group 79: RS232 communication
79-0
RS232 communication
Please contact the Technical Support team.
Group 80: IRQ_0_3
80-0
Time overflow current
control IRQ
Select longer cycle times for the current, speed and position controllers or
interpolator. Please contact the Technical Support team.
80-1
Time overflow speed
control IRQ
80-2
Time overflow position
control IRQ
80-3
Time overflow interpolator
IRQ