Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P00.12
DEC time 1
from the Max. Output frequency to 0Hz (P00.03).
Goodrive100 series inverters define four groups of ACC/DEC
time which can be selected by P05. The factory default
ACC/DEC time of the inverter is the first group.
Setting range of P00.11 and P00.12:0.0~3600.0s
Depend on
the motor
type
○
P00.13
Running
direction
selection
0: Runs at the default direction, the inverter runs in the
forward direction. FWD/REV indicator is off.
1: Runs at the opposite direction, the inverter runs in the
reverse direction. FWD/REV indicator is on.
Modify the function code to shift the rotation direction of the
motor. This effect equals to the shifting the rotation direction
by adjusting either two of the motor lines (U, V and W). The
motor rotation direction can be changed by QUICK/JOG on
the keypad. Refer to parameter P07.02.
Note:
When the function parameter comes back to the
default value, the motor’s running direction will come back to
the factory default state, too. In some cases it should be used
with caution after commissioning if the change of rotation
direction is disabled.
2: Forbid to run in reverse direction: It can be used in some
special cases if the reverse running is disabled.
0
○