3 Installation Guidelines
The chapter describes the mechanical installation and electric installation.
Only qualified electricians are allowed to carry out what described in this chapter.
Please operate as the instructions in
Safety Precautions
. Ignoring these may cause
physical injury or death or damage to the devices.
Ensure the power supply of the inverter is disconnected during the operation. Wait for
at least the time designated until the POWER indicator is off after the disconnection if
the power supply is applied. It is recommended to use the multimeter to monitor that
the DC bus voltage of the drive is under 36V.
The installation and design of the inverter should be complied with the requirement of
the local laws and regulations in the installation site. If the installation infringes the
requirement, our company will exempt from any responsibility. Additionally, if users do
not comply with the suggestion, some damage beyond the assured maintenance range
may occur.
3.1 Mechanical installation
3.1.1 Installation environment
The installation environment is the safeguard for a full performance and long-term stable functions of the
inverter. Check the installation environment as followings:
Environment
Conditions
Installation site
Indoor
Environment
temperature
0
℃
~
+
40
℃
, and the temperature changing rate is less than 0.5
℃
/minute.
If the ambient temperature of the inverter is above 40
℃
, derate 3% for every
additional 1
℃
.
It is not recommended to use the inverter if the ambient temperature is