Goodrive100 inverters
Appendix C
IKR Aandrijven en Besturen
www.ikr-industries.nl
Type
Braking unit type
100% of
braking
rate
(
Ω
)
The cousumped power of the
braking resistor
Mini
Braking
Resistor
(
Ω
)
10%
braking
50%
braking
80%
braking
GD100-2R2G-4
290.9
0.33
1.65
2.64
130
GD100-004G-4
160.0
0.6
3
4.8
80
GD100-5R5G-4
116.4
0.75
4.125
6.6
60
GD100-7R5G-4
85.3
1.125
5.625
9
47
GD100-011G-4
58.2
1.65
8.25
13.2
31
GD100-015G-4
42.7
2.25
11.25
18
23
Note:
Select the resistor and power of the braking unit according to the data our company provided.
The braking resistor may increase the braking torque of the inverter. The resistor power in the above table is
designed on 100% braking torque and 10% braking usage ratio. If the users need more braking torque, the
braking resistor can decrease properly and the power needs to be magnified.
Never use a brake resistor with a resistance below the minimum value specified
for the particular drive. The drive and the internal chopper are not able to handle
the overcurrent caused by the low resistance.