Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
can receive the frame, but the salve doesn’t answer.
The communication address of the drive is unique in the
communication net. This is the fundamental for the point to
point communication between the upper monitor and the
drive.
Note:
The address of the slave cannot set to 0.
P14.01
The
communication
baud ratio of
the drive
Set the digital transmission speed between the upper monitor
and the inverter.
0:1200BPS
1:2400BPS
2:4800BPS
3:9600BPS
4:19200BPS
5:38400BPS
Note:
The baud rate between the upper monitor and the
inverter must be the same. Otherwise, the communication is
not applied. The bigger the baud rate, the quicker the
communication speed.
4
○
P14.02
Digital bit
checkout
setting
The data format between the upper monitor and the inverter
must be the same. Otherwise, the communication is not
applied.
1
○