Goodrive100 inverters
Fault tracking
IKR Aandrijven en Besturen
www.ikr-industries.nl
STo
Maladjustment fault
1. The control parameters of the
synchronous motors not set
properly.
2. The autoturn parameter is not
right.
3. The inverter is not connected
to the motor.
1. Check the load and ensure it
is normal.
2. Check whether the control
parameter is set properly or not.
3. Increase the maladjustment
detection time.
END
Time reach of factory
setting
The actual running time of the
inverter is above the internal
setting running time.
Ask for the supplier and adjust
the setting running time.
PCE
Keypad
communication fault
1. The connection of the keypad
wires is not good or broken.
2. The keypad wire is too long
and
affected
by
strong
interference.
3. There is circuit fault on the
communication of the keypad
and main board.
1. Check the keypad wires and
ensure
whether
there
is
mistake.
2. Check the environment and
avoid the interference source.
3. Change the hardware and
ask for service.
DNE
Parameters
downloading fault
1. The connection of the keypad
wires is not good or broken.
2. The keypad wire is too long
and
affected
by
strong
interference.
3. There is mistake on the data
storage of the keypad.
1. Check the keypad wires and
ensure
whether
there
is
mistake.
2. Change the hardware and
ask for service.
3. Repack-up the data in the
keypad.