Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P11.07
The decreasing
ratio during
current limit
than the limit level, the inverter will accelerate to run.
Setting range of P11.05:
0:current limit invalid
1:current limit valid
2:current limit is invalid during constant speed
Setting range of P11.06:50.0~200.0%
Setting range of P11.07:0.00~50.00Hz/s
10.00Hz/s
◎
P11.08
Overload pre-
alarm of the
motor or the
inverter
The output current of the inverter or the motor is above
P11.09 and the lasting time is beyond P11.10, overload pre-
alarm will be output.
0x000
○
P11.09
Overload pre-
alarm test level
G
motor:150
%
○
P
motor:120