Goodrive100 inverters
Fault tracking
IKR Aandrijven en Besturen
www.ikr-industries.nl
4
. Remove the fan holder from the hinges.
5
. Install the new fan holder including the fan in reverse order.
6
. Restore power.
6.1.3 Capacitors
Reforming the capacitors
The DC bus capacitors must be reformed according to the operation instruction if the inverter has been
stored for a long time. The storing time is counted form the producing date other than the delivery data
which has been marked in the serial number of the inverter.
Time
Operational principle
Storing time less than 1 year
Operation without charging
Storing time 1-2 years
Connect with the power for 1 hour before first ON command
Storing time 2-3 years
Use
power
surge
to
charge
for
the
inverter
•
Add
25%
rated
voltage
for
30
minutes
•
Add
50%
rated
voltage
for
30
minutes
•
Add
75%
rated
voltage
for
30
minutes
• Add 100% rated voltage for 30 minutes
Storing time more than 3
years
Use
power
surge
to
charge
for
the
inverter
•
Add
25%
rated
voltage
for
2
hours
•
Add
50%
rated
voltage
for
2
hours
•
Add
75%
rated
voltage
for
2
hours
• Add 100% rated voltage for 2 hours
The method of using power surge to charge for the inverter: