Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Note:
1. Adjust the parameter properly to avoid the stopping
caused by inverter protection during the switching of the grid.
2. Prohibition of input phase protection can enable this
function.
P11.03
Overvoltage
speed loss
protection
0:Disabled
1:Enabled
1
○
P11.04
Overvoltage
speed loss
voltage
protection
120~150%(standard bus voltage)(400V)
140%
○
120~150%(standard bus voltage)(230V)
120%
P11.05
Current limit
action selection
The actual increasing ratio is less than the ratio of output
frequency because of the big load during ACC running. It is
necessary to take measures to avoid overcurrent fault and
the inverter trips.
During the running of the inverter, this function will detect the
output current and compare it with the limit level defined in
P11.06. If it exceeds the level, the inverter will run at stable
frequency in ACC running, or the inverter will derate to run
during the constant running. If it exceeds the level
continuously, the output frequency will keep on decreasing to
the lower limit. If the output current is detected to be lower
1
◎
P11.06
Automatic
current limit
level
G
motor:160.
0%
◎
P
motor:120.
0%