Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P08.07
Jogging
running ACC
time
The jogging ACC time means the time needed if the inverter
runs from 0Hz to the Max. Frequency.
The jogging DEC time means the time needed if the inverter
goes from the Max. Frequency (P0.03) to 0Hz.
Setting range:0.0~3600.0s
Depend on
module
○
P08.08
Jogging
running DEC
time
Depend on
module
○
P08.09
Jumping
frequency 1
When the set frequency is in the range of jumping frequency,
the inverter will run at the edge of the jumping frequency.
The inverter can avoid the mechanical resonance point by
setting the jumping frequency. The inverter can set three
jumping frequency. But this function will be invalid if all
jumping points are 0.
Setting range: 0.00~P00.03(the Max. frequency)
0.00Hz
○
P08.10
jumping
frequency
range 1
0.00Hz
○
P08.11
Jumping
frequency 2
0.00Hz
○
P08.12
Jumping
frequency
range 2
0.00Hz
○
P08.13
Jumping
frequency 3
0.00Hz
○
P08.14
Jumping
frequency
0.00Hz
○