Goodrive100 inverters
Keypad operation procedure
IKR Aandrijven en Besturen
www.ikr-industries.nl
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
3. The inverter stops when overloading or underloading.
LED hundreds :
0:Detection all the time
1:Detection in constant running
Setting range of P11.09: P11.11~200%
Setting range of P11.10: 0.1~60.0s
P11.11
Detection level
of the
underload pre-
alarm
If the inverter current or the output current is lower than
P11.11, and its lasting time is beyond P11.12, the inverter will
output underload pre-alarm.
Setting range of P11.11: 0~P11.09
Setting range of P11.12: 0.1~60.0s
50%
○
P11.12
Detection time
of the
underload pre-
alarm
1.0s
○
P11.13
Output terminal
action selection
during fault
Select the action of fault output terminals on undervoltage
and fault reset.
0x00~0x11
LED ones:
0:Action under fault undervoltage
1:No action under fault undervoltage
0x00
○