Appendix A Parameter Table
- 82 -
Param.
No.
Param. Name
Setting Range
Default
Property
F9-64 Load loss detection
level
0.0% to 100.0%
10.0%
☆
F9-65 Load loss detection
time
0.0s to 60.0s
1.0s
☆
F9-67 Overspeed detection
level
0.0% to 50.0% (maximum frequency)
(Overspeed detection is disabled when it is
set to 0.0%.)
5.0%
☆
F9-68 Overspeed detection
time
0.0s to 60.0s
1.0s
☆
F9-69 Detection level of
speed error
0.0% to 50.0% (maximum frequency)
(Overspeed detection is disabled when it is
set to 0.0%.)
20.0%
☆
F9-70 Detection time of
speed error
0.0s to 60.0s
5.0s
☆
F9-71 Power dip ride-
through gain
0 to 100
40
☆
F9-72 Power dip ride-
through integral
0 to 100
30
☆
F9-73
Deceleration time
of power dip ride-
through
0.0s to 300.0s
20.0s
☆
Group FA: Process Control PID Function
FA-00 PID reference setting
channel
0: Set by FA-01
1: AI1
2: AI2
4: Pulse setting (DIO1)
5: Communication setting (1000H)
6: Multi-reference
0
☆
FA-01 PID digital setting
0.0% to 100.0%
50.0%
☆
FA-02 PID feedback setting
channel
0: AI1
1: AI2
3: AI1-AI2
4: Pulse setting (DIO1)
5: Communication setting (1000H)
6: AI1+ AI2
7: Max. (|AI1|, |AI2|)
8: Min. (|AI1|, |AI2|)
0
☆
FA-03 PID operation direc-
tion
0: Forward
1: Reverse
0
☆
FA-04 PID reference and
feedback range
0 to 65535
1,000
☆
FA-05 Proportional gain Kp1 0.0 to 1000.0
20.0
☆
FA-06 Integral time Ti1
0.01s to 100.00s
2.00s
☆
FA-07
Differential time Td1
0.000s to 10.000s
0.000s
☆
FA-08 PID output limit in
reverse direction
0.00 Hz to the maximum frequency
2.00 Hz
☆
FA-09 PID deviation limit
0.0% to 100.0%
0.0%
☆
FA-10
PID differential limit 0.00% to 100.00%
0.10%
☆