Appendix A Parameter Table
- 66 -
Param.
No.
Param. Name
Setting Range
Default
Property
F3-15 Voltage rise time of V/
F separation
0.0s to 1000.0s
Note: It sets the time for the output voltage
to rise from 0 to the rated motor voltage.
0.0s
☆
F3-16 Voltage decline time
of V/F separation
0.0s to 1000.0s
Note: It sets the time for the output voltage
to rise from 0 to the rated motor voltage.
0.0s
☆
F3-17 Stop mode selection
for V/F separation
0: Frequency and voltage declining to 0
independently
1: Frequency declining after voltage de-
clines to 0
0
★
F3-18 V/F current limit level
50% to 200%
150%
★
F3-19 V/F current limit
selection
0: Disabled
1: Enabled
1
★
F3-20 V/F current limit gain 0 to 100
20
☆
F3-21
V/F compensation
factor of speed mul-
tiplying current limit
level
50 to 200
50
★
F3-22 V/F voltage limit
650.0 V to 800.0 V
770.0 V
★
F3-23 V/F voltage limit
selection
0: Disabled
1: Enabled
1
★
F3-24 V/F frequency gain for
voltage limit
0 to 100
30
☆
F3-25 V/F voltage gain for
voltage limit
0 to 100
30
☆
F3-26
V/F frequency rise
threshold during
voltage limit
0 to 50
5
★
F3-27 Slip compensation
time constant
0.1 to 10.0
0.5
☆
F3-28 Automatic frequency
rise
0: Disabled
1: Enabled
0
★
F3-29 Minimum motoring
torque current
10 to 100
50
★
F3-30 Maximum generating
torque current
10 to 100
20
★
F3-31 Automatic frequency
rise KP
0 to 100
50
☆
F3-32 Automatic frequency
rise KI
0 to 100
50
☆
F3-33 Online torque com-
pensation gain
80 to 150
100
★
Group F4: Input Terminals