Appendix A Parameter Table
- 68 -
Param.
No.
Param. Name
Setting Range
Default
Property
F4-11 Terminal I/O control
mode
0: Two-wire control mode 1
1: Two-wire control mode 2
2: Three-wire control mode 1
3: Three-wire control mode 2
0
★
F4-12 Terminal UP/DOWN
rate
0.001 Hz/s to 65.535 Hz/s
1.000 Hz/s
☆
F4-13 AI curve 1 minimum
input
-10.00 V to F4-15 (AI curve 1 maximum
input)
-10.00 V
☆
F4-14
Corresponding per-
centage of AI curve 1
minimum input
-100.0% to +100.0%
-100.0%
☆
F4-15 AI curve 1 maximum
input
F4-13 (AI curve 1 minimum input) to +10.00 V
10.00 V
☆
F4-16
Corresponding per-
centage of AI curve 1
maximum input
-100.0% to +100.0%
100.0%
☆
F4-17
AI1 filter time
0.00s to 10.00s
0.10s
☆
F4-18 AI curve 2 minimum
input
0.00 V to F4-20 (AI curve 2 maximum input)
0.00 V
☆
F4-19
Corresponding per-
centage of AI curve 2
minimum input
-100.0% to +100.0%
0.0%
☆
F4-20 AI curve 2 maximum
input
F4-18 (AI curve 2 minimum input) to +10.00 V
10.00 V
☆
F4-21
Corresponding per-
centage of AI curve 2
maximum input
-100.0% to +100.0%
100.0%
☆
F4-22
AI2 filter time
0.00s to 10.00s
0.10s
☆
F4-23 AI curve 3 minimum
input
0.00 V to F4-25 (AI curve 3 maximum input)
0.00 V
☆
F4-24
Corresponding per-
centage of AI curve 3
minimum input
-100.0% to +100.0%
0.0%
☆
F4-25 AI curve 3 maximum
input
F4-23 (AI curve 3 minimum input) to +10.00 V
10.00 V
☆
F4-26
Corresponding per-
centage of AI curve 3
maximum input
-100.0% to +100.0%
100.0%
☆
F4-28 Pulse minimum input 0.00 kHz to F4-30 (Pulse maximum input)
0.00 kHz
☆
F4-29
Corresponding
percentage of pulse
minimum input
-100.0% to 100.0%
0.0%
☆
F4-30 Pulse maximum input F4-28 (Pulse minimum input) to 100.00 kHz
50.00 kHz
☆
F4-31
Corresponding set-
ting of pulse maxi-
mum input
-100.0% to 100.0%
100.0%
☆
F4-32
Pulse filter time
0.00s to 10.00s
0.10s
☆