Appendix A Parameter Table
- 80 -
Param.
No.
Param. Name
Setting Range
Default
Property
F9-48 Fault protection
action selection 1
Ones: Motor overload (E11)
Tens: Reserved
Hundreds: Output phase loss (E13)
Thousands: Heatsink overheat (E14)
Ten thousands: External fault (E15)
Note: Output phase loss is valid only in V/
F control mode when decelerate to stop or
alarm is selected.
222
0: Coast to
stop
1: Decelerate
to stop
2: Restart
allowed
3: Reserved
4: Alarm
5: Canceled
★
F9-49 Fault protection
action selection 2
Ones: Communication timeout (E16)
Tens: External DC soft charge unit fault
(E17) (only for models of 90 kW and above)
Hundreds: Reserved
Thousands: Motor auto-tuning fault (E19)
Ten thousands: Reserved
50000
0: Coast to
stop
1: Decelerate
to stop
2: Restart
allowed
3: Reserved
4: Alarm
5: Canceled
★
F9-50 Fault protection
action selection 3
Ones: EEPROM read/write error (E21)
Tens: Motor auto-tuning abnormal (E22)
Hundreds: Motor short-circuited to the
ground (E23)
Thousands: Inter-phase short-circuit (E24)
Ten thousands: Power supply unit fault
(E25)
55000
0: Coast to
stop
1: Decelerate
to stop
2: Restart
allowed
3: Reserved
4: Alarm
5: Canceled
★
F9-51 Fault protection
action selection 4
Ones: Accumulative running time reached
(E26)
Tens: User-defined fault 1 (E27)
Hundreds: User-defined fault 2 (E28)
Thousands: Power-on time reached (E29)
Ten thousands: Load lost (E30)
50000
0: Coast to
stop
1: Decelerate
to stop
2: Reserved
3: Reserved
4: Alarm
5: Canceled
★