Appendix A Parameter Table
- 79 -
Param.
No.
Param. Name
Setting Range
Default
Property
F9-26 3rd fault subcode
●
F9-27 Frequency upon 2nd
fault
0.00 Hz to 655.35 Hz
0.00 Hz
●
F9-28 Current upon 2nd
fault
0.00 A to 655.35 A
0.00 A
●
F9-29 Bus voltage upon 2nd
fault
0.0 V to 6553.5 V
0.0 V
●
F9-30 DI state upon 2nd
fault
0 to 9999
0
●
F9-31 DO state upon 2nd
fault
0 to 9999
0
●
F9-32 AC drive state upon
2nd fault
0 to 65535
0
●
F9-33 Power-on time upon
2nd fault
0s to 65535s
0s
●
F9-34 Running time upon
2nd fault
0.0s to 6553.5s
0.0s
●
F9-35 IGBT temperature
upon 2nd fault
0.0 V to 6553.5 V
0.0 V
●
F9-36 2nd fault subcode
●
F9-37 Frequency upon 1st
fault
0.00 Hz to 655.35 Hz
0.00 Hz
●
F9-38 Current upon 1st fault 0.00 A to 655.35 A
0.00 A
●
F9-39 Bus voltage upon 1st
fault
0.0 V to 6553.5 V
0.0 V
●
F9-40 DI state upon 1st fault 0 to 9999
0
●
F9-41 DO state upon 1st
fault
0 to 9999
0
●
F9-42 AC drive state upon
1st fault
0 to 65535
0
●
F9-43 Power-on time upon
1st fault
0s to 65535s
0s
●
F9-44 Running time upon
1st fault
0.0s to 6553.5s
0.0s
●
F9-45 IGBT temperature
upon 1st fault
0.0 V to 6553.5 V
0.0 V
●
F9-46 1st fault subcode
●
F9-47 Fault protection
action selection 0
Ones: Overcurrent during acceleration
(E02)
Tens: Overvoltage during acceleration
(E05)
Hundreds: Reserved
Thousands: undervoltage (E09)
Ten thousands: AC drive overload (E10)
Note: Output phase loss is valid only in V/
F control mode when decelerate to stop or
alarm is selected.
22022
0: Coast to
stop
1: Decelerate
to stop
2: Restart
allowed
3: Reserved
4: Alarm
5: Canceled
★