Appendix A Parameter Table
- 58 -
Appendix A Parameter Table
☆ : The parameter can be modified when the AC drive is in either stop or running state.
★ : The parameter cannot be modified when the AC drive is in the running state.
● : The parameter is the actual measured value and cannot be modified.
*: The parameter is a factory parameter and can be set only by the manufacturer.
A.1 Standard Parameter Table
Param.
No.
Param. Name
Setting Range
Default
Property
Group F0: Standard Parameters
F0-00 G/P type display
1: G type (constant torque load)
1
●
F0-01 Motor 1 control mode
0: Sensorless vector control (SVC)
1: Reserved
2: V/F control
0
★
F0-02 Command source
selection
0: External LCD panel/Commissioning
software
1: Terminal I/O control
2: Communication control
0
★
F0-03 Main frequency refer-
ence X selection
0: Digital setting (initial value F0-08 can be
modified by keypad or terminal UP/DOWN,
non-retentive at power failure)
1: Digital setting (initial value F0-08 can be
modified by keypad or terminal UP/Down,
retentive at power failure)
2: AI1
3: AI2
4: (Reserved)
5: Pulse setting (DIO1)
6: Multi-reference
7: Simple PLC
8: PID
9: Communication setting
10: Synchronization control
11: Air compressor control
11
★