FC6A S
ERIES
MICROS
MART
U
SER
’
S
M
ANUAL
FC9Y-B1722
2-13
2: P
RODUCT
S
PECIFICATIONS
Self-diagnostic Functions
Input Filter
0 ms (no filter), 3 to 15 ms selectable (in 1 ms increments)
Catch Input/Interrupt Input
High-speed Counter
Pulse Output (Transistor Output Type Only)
Function Switch
Run/Stop Methods
Keep data
User program (ROM) CRC check
Timer/counter preset value change check
User program syntax check
User program execution check
Watchdog timer check
User program download check
Power failure
Clock error
Data link connection check
Expansion bus initialization check
System check
SD memory card transfer check
SD memory card access check
High-speed 4 Points (I0, I1, I6, I7)
Minimum turn on pulse width:
5
μ
s
Minimum turn off pulse width:
5
μ
s
Medium-speed 2 Points (I3, I4)
Minimum turn on pulse width:
35
μ
s
Minimum turn off pulse width:
35
μ
s
Maximum Counter
Frequency and Points
Single-phase, two-phase common:
100 kHz (single-phase 4 points max, two-phase 2 points max)
Single-phase dedicated:
5 kHz (2 points)
Count Range
Single-phase, two-phase common:
0 to 4,294,967,295 (32 bits)
Single-phase dedicated:
0 to 4,294,967,295 (32 bits)
Operation Mode
Rotary encoder mode, adding counter mode, frequency measurement mode
Part No.
FC6A-C16K1CE
FC6A-C16P1CE
FC6A-C24K1CE
FC6A-C24P1CE
FC6A-C40K1CE
FC6A-C40P1CE
FC6A-C40K1DE
FC6A-C40P1DE
FC6A-C40K1CEJ
FC6A-C40P1CEJ
FC6A-C40K1DEJ
FC6A-C40P1DEJ
Points
4
Maximum output
pulse frequency
Q0,Q1: 100kHz
Q2,Q3: 5kHz
Q0,Q2,Q4,Q6: 100kHz
Reversible control
Single-pulse output mode: 2axis (Q0-Q3)
Dual-pulse output mode: 1axis (Q0-Q1)
Single-pulse output mode: 4axis (Q0-Q7)
Dual-pulse output mode: 4axis (Q0-Q7)
PWM output
Duty cycle: 0.1 to 100.0 (increments of 0.1%)
Output pulse frequency: 15 to 5,000 (increments of 1Hz)
: 4 points(Q0-Q3)
*Q0,Q1:Adjust min. 5
μ
s as ON time, and min. 15
μ
s as OFF time.
*Q2,Q3:Adjust min. 100
μ
s as ON/OFF time .
Duty cycle: 0.1 to 100.0 (increments of 0.1%)
Output pulse frequency: 15 to 5,000
(increments of 1Hz)
: 4 points(Q0,Q2,Q4,Q6)
*Adjust min. 5
μ
s as ON time, and min. 15
μ
s
as OFF time.
Points
1 (2 position slide switch)
Function
Program run/stop
The function can be set in the function area settings (default setting: enabled).
Power on/off
WindLDR RUN/STOP command
Function switch operation
Special internal relay (M8000) operation
Operation of stop input and reset input
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1722 8 FC6A SERIES User s Manual...
Page 12: ...TABLE OF CONTENTS Preface 11 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 182: ...2 PRODUCT SPECIFICATIONS 2 152 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 434: ...8 INSTRUCTIONS REFERENCE 8 18 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 520: ...11 SD MEMORY CARD 11 54 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 554: ...13 TROUBLESHOOTING 13 26 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 567: ...FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722 A 13 APPENDIX ASCII Character Code Table...