Analog Input Parameter Setting Values
The parameter setting values are as follows.
Signal type
If the setting value is outside the range, a parameter setting error will occur.
Data type
If the setting value is 4 to 65,535, a parameter setting error will occur.
Minimum and maximum values
The minimum and maximum values can be set only when the data type is set to optional range. Set the minimum and maximum
values between -32,768 and 32,767. However, when signal type is set to PTC thermistor (threshold), set it 1, 2, or 4.
Setting Value
Signal Type
0
Unused
1
0 to 10 V
2
-10 to +10 V
3
0 to 20 mA
4
4 to 20 mA
5
Type K thermocouple
6
Type J thermocouple
7
Type R thermocouple
8
Type S thermocouple
9
Type B thermocouple
10
Type E thermocouple
11
Type T thermocouple
12
Type N thermocouple
13
Type C thermocouple
14
Pt100
15
Pt1000
16
NI100
17
NI1000
18
NTC thermistor
19
PTC thermistor
20
PTC thermistor (threshold)
21
Resistance measurement
22
Expansion 0 to 20 mA
23
Expansion 4 to 20 mA
Setting Value
Data type
0
Binary data/Binary data (12 bits)
1
Optional range/Optional range (12 bits)
2
Celsius/resistance/Binary data (16 bits)
3
Fahrenheit/Optional range (16 bits)
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1722 8 FC6A SERIES User s Manual...
Page 12: ...TABLE OF CONTENTS Preface 11 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 182: ...2 PRODUCT SPECIFICATIONS 2 152 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 434: ...8 INSTRUCTIONS REFERENCE 8 18 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 520: ...11 SD MEMORY CARD 11 54 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 554: ...13 TROUBLESHOOTING 13 26 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 567: ...FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722 A 13 APPENDIX ASCII Character Code Table...