5: F
UNCTIONS
AND
S
ETTINGS
5-44
FC6A S
ERIES
MICROS
MART
U
SER
’
S
M
ANUAL
FC9Y-B1722
Analog Voltage Input
The section describes the analog input built into the FC6A Series MICROSmart.
Function Description
The FC6A Series MICROSmart is equipped with a built-in analog voltage input function. This function acquires 0 to 10V DC voltage
analog input by converting it to a digital value. The converted analog signal is stored in a special data register. Only one analog
input can be used.
Analog input value storage location
The converted analog signal is stored in a special data register (D8058: read-only) as a digital value. This digital value is updated with
each scan. The range of the value that is stored in the special data register (D8058: read-only) can be specified with the data type.
Analog input status (D8060)
The analog input status code is stored in special data register D8060 (analog input status).
Analog Input Filter
The analog input data is averaged by the specified filter count. This can reduce rapid fluctuations in analog input.
The larger this value is set, the slower the tracking of the change in analog input becomes.
When filtering, the input value is calculated with the equation below.
Analog input data types
The range of analog values that can be handled with the specified data types are as follows.
Status code
Details
Analog Input Value
0
Normal operation
Current analog input value
1
Converting data
(occurs only once during the initial conversion when the power is turned on)
Undefined
2
Initializing
0
5
Wiring fault (out of maximum range)
When the analog input value exceeds 11 V
Upper limit value
3, 4, 6 to 65,535
Reserved
—
Count
Details
1 to 255
The input value is set as the average value of n samples of analog input data. (n: Count)
Details
Data type
All-in-One CPU Module
Plus CPU Module
Binary data
0 to 1,000
0 to 4,000
Optional range
Minimum to maximum
(The minimum and maximum in a range between 0 to
1,000 where minimum
≤
maximum)
Minimum to maximum
(The minimum and maximum in a range between -32,768
to 32,767 where minimum
≤
maximum)
+ (Red)
– (Black)
External Device
(Voltage Input)
Analog Input
Analog input value after filtering =
Total analog input values for filter count (n) worth of scans
Filter count n
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1722 8 FC6A SERIES User s Manual...
Page 12: ...TABLE OF CONTENTS Preface 11 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 182: ...2 PRODUCT SPECIFICATIONS 2 152 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 434: ...8 INSTRUCTIONS REFERENCE 8 18 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 520: ...11 SD MEMORY CARD 11 54 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 554: ...13 TROUBLESHOOTING 13 26 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 567: ...FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722 A 13 APPENDIX ASCII Character Code Table...