5: F
UNCTIONS
AND
S
ETTINGS
5-10
FC6A S
ERIES
MICROS
MART
U
SER
’
S
M
ANUAL
FC9Y-B1722
Run/Stop Selection at Power Up
Start control special internal relay M8000 maintains its status when the FC6A Series MICROSmart is powered down. When
powered up, the FC6A Series MICROSmart is started or stopped according to the M8000 status. The Run/Stop Selection at Power
Up is used to select whether to start or stop the FC6A Series MICROSmart regardless of the M8000 status when the FC6A Series
MICROSmart is powered up.
Stop and reset inputs and function switch have priority over
Run/Stop Selection at Power Up
. When the memory backup error
occurs, the FC6A Series MICROSmart is started or stopped according to Run/Stop Selection at Memory Backup Error regardless of
Run/Stop Selection at Power Up. For start/stop operation, see
"Start/Stop Operation" on page 4-15
.
Since this settings relate to the user program, the user program must be downloaded to the FC6A Series MICROSmart after
changing this settings.
Programming WindLDR
1.
From the WindLDR menu bar, select
Configuration
>
Run/Stop Contro
l
.
The
Function Area Settings
dialog box for Run/Stop Control appears.
2.
Click the button under Run/Stop Selection at Power Up.
Keep Run/Stop State at Power Down (Default):
Click this button to keep the run/stop status at power down when the FC6A Series MICROSmart is powered up.
Run (M8000 is turned on):
Click this button to always start the FC6A Series MICROSmart when the FC6A Series MICROSmart is powered up. However, when the function to
control running and stopping the FC6A Series MICROSmart is set for the function switch, the function switch must be set to 1.
Stop (M8000 is turned off):
Click this button to always stop the FC6A Series MICROSmart when the FC6A Series MICROSmart is powered up.
3.
Click
OK
.
This concludes configuring the settings.
This example designates
Keep Run/Stop Status at
Power Down.
Resets all Function Area Settings
values to defaults.
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1722 8 FC6A SERIES User s Manual...
Page 12: ...TABLE OF CONTENTS Preface 11 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 182: ...2 PRODUCT SPECIFICATIONS 2 152 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 434: ...8 INSTRUCTIONS REFERENCE 8 18 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 520: ...11 SD MEMORY CARD 11 54 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 554: ...13 TROUBLESHOOTING 13 26 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 567: ...FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722 A 13 APPENDIX ASCII Character Code Table...